Case study

Deep geothermal with a large heat pump

Dipl.-Ing. Heiko Reder · Energy engineer · Co-developer of Toolmeyer · As of: 17 Nov 2026

A geothermal plant with 100 °C brine and a large heat pump delivers around 20 MW of district heating with a seasonal performance factor of the whole plant of 6.6. The production pump needs almost as much power as the heat pump. This only becomes visible when all consumers are in one balance.

Task

Check whether a deep geothermal plant with a downstream large heat pump can supply a district heating network with 90 °C flow, and what seasonal performance factor the whole plant achieves.

Plant

Component Design
Geothermal brine 250 t/h, 100 °C, lifted over 1,100 m of height through 1,200 m of pipe
Production pump 1 × 100 %, Δp 120 bar
Heat exchanger WT1 plate heat exchanger, direct use
Large heat pump centrifugal compressor, refrigerant R1234ze(E), sink 90 °C
Reinjection pump 1 × 100 %, Δp 10 bar
District heating return 55 °C, 460 t/h, network pumps 3 × 50 %
Load cases winter 3,000 h, transition 3,000 h, summer 2,000 h

Result

Figure Winter Transition Summer Year
Heat to district heating 20.2 MW 16.6 MW 7.4 MW 125 GWh/a
Overall plant COP 6.29 6.97 6.91 SPF 6.62
Heat pump COP 5.09 5.83 5.42 SPF 5.34
Electrical auxiliary consumption 3,214 kW 2,392 kW 1,078 kW 19.0 GWh/a

In winter the auxiliary consumption is split as follows:

Consumer Electrical power Share
Large heat pump 1,580 kW 49 %
Production pump 1,438 kW 45 %
Reinjection pump 105 kW 3 %
District heating network pumps 91 kW 3 %

Finding

With a production pump assumed at a flat 20 bar, the balance showed an overall plant COP of 9.5 in winter. With the real lift and pipe length (120 bar) it drops to 6.3. Anyone looking only at the heat pump clearly overestimates the economics. Toolmeyer shows this because pumps, heat exchangers and heat pump are calculated in one model and the value table summarises all load cases with annual values.

What separate tools would have required

Step separate tools Toolmeyer
Brine and district heating balance balance program one diagram
Heat pump with refrigerant manufacturer tool or own model large heat pump component
Pump power spreadsheet calculated in the diagram
Seasonal performance factor spreadsheet with transferred values value table with hours per load case
Process flow diagram with 3 × 50 % pumps and KKS by hand in CAD derived automatically

Calculate it yourself

The example is freely available in the heat balance tool: Open in the tool · Description of the example

Based on the public example with general values, not a client project. Figures as of 15 Nov 2026, calculation state of the heat balance tool.