Large heat pump in a district heating network

How much power does a large heat pump need, what does its heat cost and how much does it save compared with a gas boiler? Choose the heat source and network temperatures, enter prices, read the result.

Heat pump

Comparison: heat from a gas boiler

Investment

Heat cost depending on the power price. Dot: your input. Where the lines cross is the power price above which the gas boiler becomes cheaper.
Large heat pump (incl. capital, maintenance)Gas boiler (fuel, CO₂)

No warranty: rough calculation with simplified models and your assumptions. It does not replace a design, a quotation or a project feasibility study. Checking and using the results is the responsibility of the user.

Next step

Calculate the heat pump in the network in detail?

In the heat balance tool you calculate the large heat pump with real refrigerant data, load cases over the year and its integration into the network. The example is ready-built.

Open the example

How the large heat pump calculator works

A large heat pump takes heat from a low-temperature source, for example river water, wastewater or waste heat, and raises it with electrical energy to the flow temperature of the district heating network. How much power it needs for this is given by the coefficient of performance (COP): heat output divided by electrical power.

1. COP from the Lorenz cycle

In district heating the temperatures change on both sides: the network water is heated from return to flow, and the source cools down. The calculator therefore uses the logarithmic mean temperatures of both sides (Lorenz cycle) with 3 K approach temperature each and multiplies the ideal COP by the quality grade. Built large heat pumps usually reach 45 to 60 % of the Lorenz value.

The most important lever is the temperature lift: every kelvin less flow temperature or more source temperature noticeably improves the COP. This is why lowering network temperatures almost always pays off when transforming a heating network.

2. Heat cost compared

The heat cost of the heat pump is made up of power (power price divided by COP), capital (annuity of the investment after subsidy) and maintenance, minus any operating subsidy. It is compared with heat from an existing gas boiler: gas and CO₂ price divided by the boiler efficiency, without investment.

3. What the calculator does not cover

Part load, minimum load and cycling, varying source and network temperatures over the year, hourly power prices, storage and the exact conditions of subsidy programmes. You can calculate these in the heat balance example “Large heat pump in district heating” with three load cases and real refrigerant data.

Frequently asked questions

What COP does a large heat pump reach in district heating?

That depends mainly on the temperature lift. With river water at around 10 °C as the source and 90 °C flow temperature, the COP is typically 2.5 to 3; with waste heat at around 30 °C it is 3.5 to 4.5. The lower the network temperature, the better.

What does a large heat pump cost?

For plants in the megawatt range, roughly €500 to €1,500 per kW of heat output are quoted, depending on heat source, refrigerant, integration and construction. The calculator uses your value; without a quotation it is only an assumption.

Which heat sources are suitable?

River water, lake water, treated wastewater, groundwater, waste heat from industry and data centres, geothermal brine downstream of a geothermal plant, and ambient air. Yield, permits and temperature over the year decide the choice.

Are there subsidies for large heat pumps?

In Germany, the federal funding programme for efficient heating networks (BEW) subsidises investment in heating networks and generators and, for heat pumps, also operation. Other countries have their own programmes. Enter the rates in the calculator as a percentage or €/MWh.

What does the calculator cost?

Nothing. It is free to use without sign-up. Found a bug or have a wish? Post it on the feedback page.

← All free calculators

Transparency

How we calculate

  • Real refrigeration cycle with properties from CoolProp (Helmholtz reference equations)
  • Water to IAPWS-IF97 for source and sink
  • Levelised cost of heat with annuity, subsidy, maintenance and seasonal performance factor – all formulas open
  • Guide values clearly marked: compressor efficiencies and part load do not replace manufacturer data
See the calculation basis